VITALink

  • UL Listed
  • UL Electrical Circuit Integrity System (FHIT 120)
  • NEC Type MC
  • NFPA 130 & 502
  • Low smoke zero halogen
  • VITALink MC Transit
    Image: VITALink MC Transit

Exane VITALink MC Transit is an armoured power cable with a 2 hour fire-rating. A low smoke zero halogen jacket surrounds corrugated welded copper armour and Fire-Roc insulation to give the annealed copper wire maximum protection. VITALink is a multi core self-contained cable which is easy to install – no cutting, deburring, no bending or wire pulling is needed, it fits directly from the reel without needing any special equipment. It’s ideal for use in ventilation, lighting and communications circuits.

*Rated 90°C for normal operation, 130°C for emergency overload conditions and 250°C for short circuit conditions.

 

Watch the VITALink video here 

At a glance

  • 2-hour fire rating
  • Available as a VFD cable with segmented grounds
  • Simple to terminate with commercially available brass or stainless steel MC connectors
  • Uses conventional tools for terminating
  • Printed number coding allows for easy circuit identification
  • Available in long lengths
  • Welded armour forms an impervious barrier
  • Armour is impact and crush resistant
  • Fire-rated splice available (FHIT 120)

Performance standards

  • UL listed, NEC Type MC in accordance with UL Standard 1569
  • UL listed as 2-hour fire rated in accordance with ANSI/UL 2196, maximum 480 volts under fire conditions
  • Electrical Circuit Integrity Systems (FHIT) — System No. 120 of the UL Fire Resistance Directory
  • Meets and exceeds fire rated cable requirements in NFPA 130 for Transit applications and NFPA 502 for Highway Tunnel applications
  • Complies with NFPA 130 and NFPA 502 for total smoke released and low toxicity
  • For use in wet locations to 90°C
  • Rated FT-4/IEEE 1202 vertical flame test; ST1, limited smoke
  • Armoured with copper sheath that exceeds the NEC requirement for equipment grounding conductor

Construction

  • Conductor: Annealed copper, Class “B” strand per ASTM B-170 and B-8
  • Insulation: Thermoset, low smoke zero halogen silicone rubber
  • Circuit Identification: Printed numbers per ICEA Method 4
  • Inner Jacket: Thermoset, low smoke zero halogen silicone rubber
  • Armour: Continuously welded and corrugated copper
  • Outer Jacket: Black low smoke, zero halogen polyolefin (colours available on request)

Sales at Goldwing

Our sales team has years of technical experience, enabling us to deliver a personal and professional service.

  • No minimum order quantity for our bespoke service
  • Cable cut to your required length
  • Vast stock holdings mean next day delivery

Call our sales team today to discuss your requirements.

01502 713 161
Cookies

We use cookies to help improve our website. By continuing to use this website, you agree to our use of cookies.